|
For
a 40 story office property built in 1965 and having 1,000 or more
feet of 12 in. condenser riser piping, the total loss of more than
5,000 lbs. of steel into the circulating system can be shown. See
the below table for the weight losses of various pipe sizes and
corrosion rates.

Often, a low to moderate corrosion
rate will present no threat to the integrity of the pipe itself,
yet may still damage the piping system after many years or decades
of operation. At a constant 5 MPY corrosion rate, for example, 12
in. schedule 40 condenser water pipe will last well past 45 years
before reaching 0.175 in. - its minimum acceptable wall thickness
under most conditions. Yet, that same 5 MPY corrosion rate still
presents a very serious threat.
Since the corrosion of steel produces
a significantly greater volume of less dense iron oxide, serious
secondary problems can be created unless such deposits are continuously
removed. Interior deposits can produce even more serious problems
at closed systems - where no blowdown exists and no indication is
given. Corrosion problems are often localized, and a gradual build-up
of deposits in the lower floor horizontal lines due to a low 1 MPY
system wide corrosion rate can produce random but severe wall losses
at rates well above 25 MPY - leading to premature pipe failure.
Correcting A Problem
Unquestionably, removing all existing
deposits of iron oxide, which can total in the thousands of pounds
for even a medium sized commercial building system, should become
the most important focus in addressing any corrosion problem. Aside
from lost heat transfer, clogged strainers, restricted flows, and
other operating problems, interior surface deposits greatly accelerate
pipe loss by preventing corrosion control chemicals from reaching
the base steel, and by initiating various secondary corrosion mechanisms.
  
Due to the large volume of deposits typically produced by any
corrosion condition, the addition of supplemental filtration is
mandatory - with the option of filtering the greatest possible volume
of water preferred over capturing the smallest micron particle.
Chemically removing the accumulated iron oxide by either dissolving
it for blowdown or re-suspending it for filtration capture is typically
employed, but often presents added threat to the piping and related
system components depending upon the remaining integrity of the
piping, cleaning agent, and cleanout procedure used. Greater maintenance
demands in the form of punching heat exchanger tubes, cleaning strainers
and tower pans, and added filter maintenance may be temporary, or
in the case of a severe corrosion problem, may be a permanent addition
to the operating schedule of the property.
Increased chemical inhibitor and biocide levels are generally
required, as are supplemental chemical dispersing agents. For a
microbiologically influenced corrosion (MIC) problem, repeated sterilization
and cleaning of the system will be necessary. Contracting an outside
consultant to oversee and advise the chemical treatment or cleaning
program is often advised due to the complexity of various treatment
options, conflicting claims and abilities of various chemical treatment
contractors, and the potential threat to the piping system.
Under the most severe conditions of a well established under
deposit corrosion or MIC condition, it may be impossible to save
the piping system from premature failure. In such cases, effort
usually focuses on minimizing damage and operating problems, replacing
pipe as necessary, and extending its service life as best possible.
PAGE 1 2
3 4 5
next
|